G e n e r a l T I C C o n t r o l Fe a t u r e s
Menus on the Controller:
The controller has information available in 5 areas. Four of them are user accessi-
ble. These are: the Main Menu, the Setpoint Menu, the Configuration menu and
the Alarm Page. The service page also has additional parameters that are accessible
in cases of need.
Relaying Control information via three modes:
The controller relays information via three modes.
1
The status lights indicate the state of the machine and its control components.
In the chiller these are Pump, Hot gas valve, and Compressor.
2
The digital indication of the process in temperatures and times.
3
The alpha abbreviation of the process parameters to isolate the variables and the
alarms from each other.
Main Menu
The main menu is the normal operating page. The controller always defaults to this
page after a certain amount of inactivity (buttons being pushed). The first screen is
the process variable. This is a user selectable parameter and could be the to
process, from process or an average temperature. The rest of the variables are
accessed in a circular queue using only the up and down arrow keys.
The parameters include:
Process Variable- in the units selected on the Configuration page. This parameter
has its decimal fixed to whole numbers only.
Machine State - For the Chiller this is on/off.
The To Process temperature - in units selected as above. This parameter has its
decimal fixed at 0.1º
The From Process temperature - in units selected above. This parameter has its
decimal fixed at 0.1º
There are two additional temperature indicators available for the chiller and must
be purchased separately. If installed they will indicate only the temperature of the
media to which they are exposed. These were intended to display condensing
media temperature to the chiller operator however they could display any tempera-
ture in the operating range of 0-250ºF. These temperature displays are also shown
as whole numbers. If these are not connected;
is displayed.