P051
MAX VOLUME
Use this feature to display the Reading in volumetric units rather than percent.
Enter the vessel volume between Empty (P006) and Span (P007).
e.g. 1
e.g. 2
values: 0.000 to 9999
P052
TANK DIMENSION A
Enter the height of the tank bottom if P050 = 2,3,4, or 5, or the length of one end
section of the tank if P050 = 7, in Units (P005).
values: 0.000 to 9999
P053
TANK DIMENSION L
Enter the length of the tank (excluding both end sections) if P050 = 7, in Units
(P005).
values: 0.000 to 9999
P054
LEVEL BREAKPOINTS ( Universal Volume Calculation )
Enter level breakpoints* (where volume is known) if P050 = 9 or 10
values: 0.000 to 9999
P055
BREAKPOINT VOLUMES ( Universal Volume Calculation )
Enter the volume* corresponding to each Level Breakpoint entered.
values: 0.000 to 9999
* Steps to enter a Level Breakpoint or Breakpoint Volume:
1.. Press
2. Scroll (
3. Key in the desired level or volume value.
4. Press
Technical Reference
Technical Reference
Technical Reference
Technical Reference
Refer to
Refer to
Refer to
Refer to
Page 28
If the volume = 3650 m
If the volume = 267,500 U.S. gallons, enter 267.5 (1000's of gallons).
to display the index symbol,
or
) or direct access the desired Breakpoint.
.
Volume Calculation for breakpoint value selection.
Volume Calculation for breakpoint value selection.
Volume Calculation for breakpoint value selection.
Volume Calculation for breakpoint value selection.