P210
0/4 mA SETPOINT
Use this feature to reference the minimum mA output to any point in the
measurement range. Enter the material level (referenced to Empty, P006)
corresponding to the minimum mA output. This feature is preset to 0% or 100%
of Span (P007) as determined by Operation (P001).
Typically, this value is entered in Units (P005) or percent of Span (P007). If mA
Function is set for "volume", enter the value in the Max Volume (P051) units or in
percent of Max Volume.
values: -999 to 9999
P211
20 mA SETPOINT
Use this feature to reference the 20 mA output to any point in the measurement
range between Empty (P006) and Span (P007).
Enter the material level (referenced to Empty, P006) corresponding to 20mA.
This feature is preset to 0% or 100% of Span (P007) as determined by Operation
(P001).
Typically, the value is entered in Units (P005) or percent of Span (P007). If mA
Function is set for "volume", enter the value in the Max Volume (P051) units or as
a percent of Max Volume.
values: -999 to 9999
P212
mA MIN LIMIT
Use this feature to prevent the mA output from falling below the minimum
acceptable mA input value (preset to 3.800 mA) of the device connected.
values: 0.000 to 22.00
P213
mA MAX LIMIT
Use this feature to prevent the mA output from exceeding the maximum
acceptable mA input value (preset to 20.20 mA) of the device connected.
values: 0.000 to 22.00
7ML19985AN02
SITRANS LU10 – INSTRUCTION MANUAL