PROFILE POINTER PARAMETERS
When a Profile Pointer Parameter is accessed, the Echo Lock Window scope
display changes to a Profile Pointer display. The Profile Pointer may be moved to
a number of points on the Echo Profile, to gain specific information dependent
upon the Profile Pointer Parameter used.
To move the Profile Pointer to a specific point, enter the desired value. The
Profile Pointer will move to the nearest acceptable Echo Profile point. The
Profile Pointer is preset to "0".
Alternatively, to scroll the Profile Pointer along the Echo Profile
1. Press
2.
or
P
When the Profile Pointer Parameters are exited and
mode is entered, the Profile Pointer display automatically changes back to the
Echo Lock Window display.
P817 (V) PROFILE POINTER TIME
Observe the time (in ms) between the transmit pulse and the Profile Pointer.
values: 0.000 to 9999
P818 (V) PROFILE POINTER DISTANCE
Observe the distance (in P005 Units) between the transducer face and the
Profile Pointer.
values: 0.000 to 9999
P819 (V) PROFILE POINTER AMPLITUDE
Observe the amplitude (in dB above 1µV) of the Echo Profile at the Profile Pointer
position.
values: 0 to 99