Reading Parameters (P060 to P062)

If Reading alteration is required, alter the following parameters to:
a. alter the number of decimal places displayed.
b. convert to units other than Units (P005), % of Span (P007), or Max Volume
(P051).
c. reference measurements to some point other than Empty (P006) or Span (P007).
If alteration is not required, proceed to Failsafe Parameters.
If alteration is not required, proceed to Failsafe Parameters.
If alteration is not required, proceed to Failsafe Parameters.
If alteration is not required, proceed to Failsafe Parameters.
P060
DECIMAL POSITION
Enter the maximum number of decimal places to be displayed in the Reading.
In the RUN mode, the number of decimal places displayed is automatically
adjusted (if necessary) to prevent the number of Reading digits from exceeding
display capabilities.
This value is automatically altered when Max Volume (P051) is altered.
values: 0 = no digits after the decimal point
P061
CONVERT READING
Enter the value to multiply the Reading by (before display).
This feature is preset to 1.000 (no conversion).
e.g.
Avoid entering a value that, when multiplied by the maximum current reading,
Avoid entering a value that, when multiplied by the maximum current reading,
Avoid entering a value that, when multiplied by the maximum current reading,
Avoid entering a value that, when multiplied by the maximum current reading,
values: -999 to 9999
7ML19985AN02
1 = 1 digit after the decimal point
2 = 2 digits after the decimal point
3 = 3 digits after the decimal point
If the Reading is currently displayed in feet, to display in yards, enter 3.
could exceed 5 digits before the Decimal Position
could exceed 5 digits before the Decimal Position
could exceed 5 digits before the Decimal Position
could exceed 5 digits before the Decimal Position
SITRANS LU10 – INSTRUCTION MANUAL