RELAY
FUNCTION
Level H or HH
Level L or LL
In Bounds**
Out of Bounds**
Rate of Change
Temperature
* Values shown are for illustration purposes only. Enter values which apply to your particular
Important! Relay A / B Setpoint values cannot be exactly equal.
Important! Relay A / B Setpoint values cannot be exactly equal.
Important! Relay A / B Setpoint values cannot be exactly equal.
Important! Relay A / B Setpoint values cannot be exactly equal.
P112
RELAY A SETPOINT
Enter the critical point for the desired action to occur (based on the Relay
Function selected).
values: -999 to 9999
P113
RELAY B SETPOINT
Enter the critical point for the desired action to occur (based on the Relay
Function selected).
values: -999 to 9999
7ML19985AN02
SETPOINTS
*
RELAY ACTION
A
B
85 %
70 %
15 %
30 %
80%
50%
80%
50%
+10%
+5%
-10%
-5%
60
55
-30
-25
installation.
**2% factory set hysterisis, adjustable via P116.
SITRANS LU10 – INSTRUCTION MANUAL
de-energizes
energizes
de-energizes
energizes
de-energizes
energizes
de-energizes
energizes
energizes
de-energizes
energizes
de-energizes
de-energizes
fill rate increases to 10%/min
energizes
fill rate decreases to 5%/min
de-energizes
empty rate increases to 10%/min
energizes
empty rate decreases to 5%/min
de-energizes
temperature rises to 60 °C
energizes
temperature falls to 55 °C
de-energizes
temperature falls to -30 °C
energizes
temperature rises to -25 °C
WHEN
level rises to 85%
level falls to 70%
level falls to 15%
level rises to 30%
level falls to 78%
level rises to 82%
level rises to 52%
level falls to 48%
level falls to 78%
level rises to 82%
level rises to 52%
level falls to 48%
Page 37