From the "Main screen":
Zone
Menu
– press the
Menu
screen
– turn the
encoder to select the "TECHNICAL" menu
GENERAL SETTINGS
INFORMATION
TECHNICAL
Esc
– press the
click
encoder to access the modifiable area. The
following screen is displayed:
Confirm operation?
Cancel
– press the
Confirm
– turn the
encoder to select the "Zone heating" submenu
Zone heating
Ht-boiler adjust. param.
Hot water
Boiler parameters
Advanced parameters Ht
Esc
40
Thu 18 Set 2014
10:30
Off
Mode
button to view the "Menu" selection
MENU
[...]
[...]
[...]
Back
CONFIRM REQUEST
Confirm
button to access the submenus
TECHNICAL
[...]
[...]
[...]
[...]
[...]
Back
– press the
click
ters area
Fig. 83
– press and turn the
specified below:
Req. from ext. TA
Req. with room probe
Mod. with room probe
Mod. with ext. probe
Fig. 84
– press the
and return to the "Main screen".
The main control panel (MCP) then becomes a simple system op-
Fig. 85
erator with the relevant operating logic, and requests for heat
for each zone are managed by the individual chrono-thermo-
stats or ambient thermostats.
5.14.3 EXAMPLE of use of the command/control de-
vice on some types of heating systems
KEY
M
System delivery
R
System return
Pcp
Main control panel (remote)
SE
External sensor
TA2
Air thermostat for boiler activation
Fig. 86
TZ1÷TZ3 Air thermostat for the zone
VZ1-VZ3 Zone valves
RL1-RL3 Zone relays
P1-P3
Zone pump
SP
Hydraulic separator
encoder to access the modifiable parame-
Zone heating
Req. from ext. TA
NO
Room probe run
YES
Room probe modul.
YES
Ext. probe modul.
YES
Weather comp.curve
4.0
Esc
BACK
encoder to change the settings as
Zone heating
Req. from ext. TA
YES
Room probe run
NO
Room probe modul.
NO
Ext. probe modul.
YES
Esc
BACK
button to complete the modification
Esc
Fig. 87
SI
NO
NO
SI
Fig. 88