Internal Controller Functions - Danfoss VLT FC 100 Instruction Manual

110–400 kw d-frame hvac drive
Hide thumbs Also See for VLT FC 100:
Table of Contents

Advertisement

Introduction

1.5 Internal Controller Functions

1
1
Figure 1.4 is a block diagram of the adjustable frequency
drive's internal components. See Table 1.3 for their
functions.
Figure 1.4 Adjustable Frequency Drive Block Diagram
1-4
®
VLT
HVAC Drive D-Frame
Instruction Manual
Area
1
2
3
4
5
6
7
8
Table 1.3 Adjustable Frequency Drive Internal Components
®
MG16D222 - VLT
is a registered Danfoss trademark
Title
Mains input
Three-phase AC line power
supply to the adjustable
frequency drive
Rectifier
The rectifier bridge converts
the AC input to DC current to
supply inverter power
DC bus
Intermediate DC bus circuit
handles the DC current
DC reactors
Filter the intermediate DC
circuit voltage
Prove line transient protection
Reduce RMS current
Raise the power factor
reflected back to the line
Reduce harmonics on the AC
input
Capacitor bank
Stores the DC power
Provides ride-through
protection for short power
losses
Inverter
Converts the DC into a
controlled PWM AC waveform
for a controlled variable
output to the motor
Output to motor
Regulated three-phase output
power to the motor
Control circuitry
Input power, internal
processing, output, and motor
current are monitored to
provide efficient operation
and control
User interface and external
commands are monitored and
performed
Status output and control can
be provided
Functions