Control Terminal Programming Examples - Danfoss VLT FC 100 Instruction Manual

110–400 kw d-frame hvac drive
Hide thumbs Also See for VLT FC 100:
Table of Contents

Advertisement

Programming
Figure 5.10 shows the wiring connections used to enable
this set-up.
53
6-1*
U - I
A53
55
Figure 5.10 Wiring Example for External Device Providing 0–10 V
Control Signal
5.3 Control Terminal Programming
Examples
Control terminals can be programmed.
Each terminal has specified functions it is capable
of performing.
Parameters associated with the terminal enable
the function.
For proper adjustable frequency drive
functioning, the control terminals must be
wired properly
programmed for the intended function
receiving a signal
See Table 5.1 for control terminal parameter number and
default setting. (Default setting can change based on the
selection in 0-03 Regional Settings).
®
VLT
HVAC Drive D-Frame
Instruction Manual
The following example shows accessing Terminal 18 to see
the default setting.
+
0-10V
Figure 5.11
Figure 5.12
Figure 5.13
®
MG16D222 - VLT
is a registered Danfoss trademark
1.
Press [Main Menu] twice, scroll to parameter
group 5-** Digital In/Out and press [OK].
14.6%
Main Menu
2-** Brakes
3-** Reference / Ramps
4-** Limits / Warnings
5-** Digital In/Out
2.
Scroll to parameter group 5-1* Digital Inputs and
press [OK].
14.7%
Digital In/Out
5-0* Digital I/O mode
5-1* Digital Inputs
5-4* Relays
5-5* Pulse Input
3.
Scroll to 5-10 Terminal 18 Digital Input. Press [OK]
to access function choices. The default setting
Start is shown.
14.7%
Digital Inputs
5-10 Terminal 18 Digital
Input
[8]] Start
0.00A
1(1)
5
0.00A
1(1)
5-**
0.00A
1(1)
5-1*
5-3
5