Programming
Figure 5.10 shows the wiring connections used to enable
this set-up.
53
6-1*
U - I
A53
55
Figure 5.10 Wiring Example for External Device Providing 0–10 V
Control Signal
5.3 Control Terminal Programming
Examples
Control terminals can be programmed.
•
Each terminal has specified functions it is capable
of performing.
•
Parameters associated with the terminal enable
the function.
•
For proper adjustable frequency drive
functioning, the control terminals must be
wired properly
programmed for the intended function
receiving a signal
See Table 5.1 for control terminal parameter number and
default setting. (Default setting can change based on the
selection in 0-03 Regional Settings).
®
VLT
HVAC Drive D-Frame
Instruction Manual
The following example shows accessing Terminal 18 to see
the default setting.
+
0-10V
Figure 5.11
Figure 5.12
Figure 5.13
®
MG16D222 - VLT
is a registered Danfoss trademark
1.
Press [Main Menu] twice, scroll to parameter
group 5-** Digital In/Out and press [OK].
14.6%
Main Menu
2-** Brakes
3-** Reference / Ramps
4-** Limits / Warnings
5-** Digital In/Out
2.
Scroll to parameter group 5-1* Digital Inputs and
press [OK].
14.7%
Digital In/Out
5-0* Digital I/O mode
5-1* Digital Inputs
5-4* Relays
5-5* Pulse Input
3.
Scroll to 5-10 Terminal 18 Digital Input. Press [OK]
to access function choices. The default setting
Start is shown.
14.7%
Digital Inputs
5-10 Terminal 18 Digital
Input
[8]] Start
0.00A
1(1)
5
0.00A
1(1)
5-**
0.00A
1(1)
5-1*
5-3
5