151430-L8
7.5
Wiring IDP SLC Detectors
This section describes how to install IDP heat and smoke detectors. All detectors ship with installation
instructions. Refer to each detector's installation instructions for more detailed information.
To wire IDP detectors:
1.
Wire device bases as shown in Figure 7-4.
2.
Set the address for each device as described in Section 7.6.
Class B wiring
Figure 7-4 Heat and Smoke Detector Connection to the Panel.
IDP and SD SLC Device Installation
Caution: Do not loop wire under Terminal 1 or 2.
Break wire run to provide supervision of connections.
7-6
Class A wiring