all releasing zones. NAC [98:002] is assigned to Output Group 3.
Output Group 4 is created. Output Group 4 will be defaulted as "Interlock Release Alarm" output group for
all releasing zones. NAC circuit [98:003] is assigned to Output Group 4.
Note: The installer must define which input points will be used for detectors, manual release switches, or interlock/pressure
switches.
Note: For manual release operation, Installer must use an FM approved/ UL listed releasing manual station.
Manufacturer
Asco
T8210A107
8210G207
Table 10-3: Approved Releasing Solenoids
Part Number
24 VDC
24 VDC
Model 7641-L8
must be mounted
at the solenoid
Releasing solenoid
Use 24 VDC, UL listed model in table 10-3
1 solenoid per circuit
Figure 10-7 Wiring Configuration for Solenoid
10-16
Rating
Current
3A max
3A max
System Operation
Freq
0 Hz
0 Hz