Accessory Mounting Kits; Network Repeater Installation - Honeywell Farenhyt IFP-2000 Manual

Analog/ addressable fire system, emergency communication system
Table of Contents

Advertisement

151430-L8
The IFP-RPT-UTP repeater is used for connecting panels via unshielded twisted pair wiring up to a maximum
wiring distance of 3000 feet. The IFP-RPT-FO repeater is used for connecting panels via fiber optic cable up to a
maximum signal loss of 8dB. The IFP-RPT-FO repeater also has connections for unshielded twisted pair wiring
so that either fiber optic cable or unshielded twisted pair wiring can be used for connecting panels.
5.4.1.1

Accessory Mounting Kits

Repeaters can be mounted within the IFP-2000 cabinet or in an accessory cabinet. Accessory kits are available
that include a small cabinet with door, key, mounting hardware, 5 foot ribbon cable to connect the repeater to the
control panel and the repeater printed circuit board. The accessory kits are available if you want to install the
repeater outside of the IFP-2000 cabinet.
The accessory kit part numbers are:
1.
IFP-RPT-UTP-KIT which includes the IFP-RPT-UTP repeater card and SK2190
enclosure.
2.
IFP-RPT-FO-KIT which includes the IFP-RPT-FO repeater card and SK2190 enclosure.
5.4.2

Network Repeater Installation

The network repeater is designed to mount on one of the 5815XL standoff sets.
Use the following steps to properly mount the network repeater to the IFP-2000.
1.
Place the network repeater on one of the 5815XL standoff sets. Use the standoff extenders provided for bet-
ter access to the fiber optic cables if there is a clearance issue.
2.
Use the 20" ribbon cable to connect the IFP-2000 to the repeater board. Run an insulated wire from the
screw terminal labeled G (TB2) on the repeater to an earth screw terminal on the control panel.
Figure 5-5 Panel to Networked repeater connection