Model IFP-2000/ECS Installation Manual
Section 8

Programming Overview

This section of the manual is intended to give you an overview of the programming process. Please read this
section of the manual carefully, especially if you are programming the control panel for the first time.
The JumpStart Autoprogramming feature automates many programming tasks and selects default options for the
system. You should run JumpStart at least once when you are installing the system. See 8.2 for details. After you
run JumpStart, you may need to do some additional programming depending on your installation. Section 9 of
this manual covers manual programmable options in detail.
Programming the panel can be thought of as a four part process. You must program:
Network options. These affect how all panels in the network work together. (see Section 6 Network
Management for details).
System options. These are options that affect general operation of the panel. (see Section 9.6 for details).
Options for input points and zones. These are primarily options that control the detection behavior of
devices. (see Section 9.3 and Section 9.5 for details).
Options for output points and groups. This includes selecting characteristics for output groups and mapping
output circuits to output groups. (see Section 9.4 for details).
8.1

Security and Data Protection

Communication Security - Level 1
Stored Data Security - Level 0
Physical Security - Level 1
Access Control Security - Level 1
8.2

JumpStart AutoProgramming

The JumpStart AutoProgramming feature allows for faster system setup. When you run JumpStart
AutoProgramming, the panel searches for expanders and SLC devices not currently in the system. The new
devices are added in their default configuration. At the end of the JumpStart AutoProgramming you can choose
to not accept the new devices and go back to the configuration you had before. JumpStart AutoProgramming
saves the installer from having to program options for each device. Depending on the application, the installer
may need to make some changes after JumpStart AutoProgramming completes.
See Section 8.2.3 for complete details about running JumpStart AutoProgramming.
JumpStart is intended to be run one time only, immediately after SLC devices have been addressed and connected.
JumpStart will reset all manually programmed options to default settings. Do not run JumpStart after you have configured the
system.
8.2.1

Input Points

The first JumpStart AutoProgramming on the panel in default configuration will determine the number and type
of input points (detectors or contact monitor modules) on each SLC loop. JumpStart AutoProgramming assigns
the correct detector type (heat, ionization or photoelectric), so the installer does not need to edit the device type
for detectors. Any contact monitor modules on the system will be assigned type "Manual Pull." The installer will
8-1