Model IFP-2000/ECS Installation Manual
4.5.3

Temporary Programming Display

When an RPS-2000 is being initially setup, place an RA-2000 on the panel at address 63 and power up the panel.
This will initiate the Temporary Programming Display feature. This allows the RA-2000 to act as the main
annunciator for the RPS-2000 panel and allows access to the idle screen and menu system for programming.
While in this mode, a trouble will be annunciated through the system to indicate the feature is being utilized. This
is only available when no other annunciators are programmed into the system. When running JumpStart Auto-
programming, the system will ask if the intention is to keep the display or remove it after programming.
When using the Temporary Display is no longer necessary; power the panel off, remove the display, and re-
power the panel.
4.6

5815XL Installation

The 5815XL SLC expander lets you add additional addressable devices. The maximum number of SLC devices
per panel is 636. The number of 5815XL's is limited by the maximum number of SBUS devices.
To install the 5815XL:
1.
Make sure power is off at the panel.
2.
Mount the 5815XL in the IFP-2000 cabinet, the RPS-1000 cabinet, or the 5815RMK remote mounting kit.
Use the standoffs located under the control panel board assembly and secure with screws provided with the
5815XL. For additional information see Model RPS-1000 Installation Instructions (P/N 151153) or
5815RMK Remote Mounting Kit Installation Instructions (P/N 151391).
3.
Connect the 5815XL to the control panel. (See Section 4.6.1.)
4.
Use on-board DIP switches to select an SBUS ID#. (See Section 4.10.1.)
5.
Add the 5815XL module to the system through programming. JumpStart will add the module automatically
(see Section 8.2). You can also add it manually (see Section 9.2.2). Select a name, if desired (see Section
9.2.1.2).
You are now ready to connect SLC devices to the 5815XL (see Section 7.4).
Figure 4-17 is a drawing of the 5815XL board, showing the location of terminals and DIP switches.
DIP switches for
setting IDs
To panel via SBUS
Figure 4-17 5815XL Board
To SLC loop
4-13
151430-L8