Model IFP-2000/ECS Installation Manual
panel uses the Event Priority Table to determine which event mapping to use to control output groups. The Event
Priority Table can be modified using SKSS-2. It is strongly recommended that before each installation a risk
analysis is done by the stake holders (property owners, AHJ, occupants, etc...) to determine which events take
precedence over others.
The Event Priority Table contains the following events for modification:
Fire Manual Pull Alarm
Fire Detector Alarm
Fire Water Flow Alarm
Fire Interlock Release Alarm
Fire Zone Aux 1 Alarm
Fire Zone Aux 2 Alarm
Fire System Aux 1 Alarm
Fire System Aux 2 Alarm
CO Alarm
Fire Pre-Alarm
Fire Interlock Alert
Fire Supervisory
CO Supervisory
Trouble
Site F Key Status
System Status
Note: Status Points, Status Voice Aux 1, Status Voice Aux 2, and Background Music are contained within the System Status
event priority.
Note: All fire, emergency and system troubles are prioritized into the Trouble event priority.
10.5.4

Priority Rules

1.
Event priorities can be changed only within, not between, priority levels (defined by bold lines in Table 10-
1).
2.
Emergency LOC Alarm must always higher than Emergency 1-8 Point Alarm and Emergency Voice Aux 1-
4 Alarm.
3.
ECS events do not need to be in order by ECS number.
There will be at least 15 messages selectable for each standard event.
10.5.5

Other Priority Considerations

There are other considerations to take into account when the same event is acting on the same output group (an
event being mapped to an output group.) These are prioritized in order of appearance:
For voice system utilizing dual channel, normal mapping takes priority over alert mapping. Example: Zone 1
Table 10-1: Event Priority Table
Fire System
10-9
Emergency System
Emergency LOC Alarm
Emergency 1 Point Alarm
Emergency 2 Point Alarm
Emergency 3 Point Alarm
Emergency 4 Point Alarm
Emergency 5 Point Alarm
Emergency 6 Point Alarm
Emergency 7 Point Alarm
Emergency 8 Point Alarm
Emergency Voice Aux 1 Alarm
Emergency Voice Aux 2 Alarm
Emergency Voice Aux 3 Alarm
Emergency Voice Aux 4 Alarm
Emergency Supervisory
151430-L8