Removing the Remaining Packing Materials
Now that you have installed the library chassis and powered on the system, you MUST
remove the hand restraint and restraining bolt from the library chassis before the library is
operational.
1 Put on an antistatic wrist strap and clip it to the library chassis.
Take standard ESD precautions when performing this procedure.
Caution:
2 When the library powers on for the first time, the OCP asks you:
"Hand Restraint Found. Please Remove! Starting Shutdown..."
The library waits approximately 30 seconds for you to open the doors and remove
both magazines from the library. When you open the doors, the OCP displays a
message telling you that the doors are open.
If you are unable to remove the magazines before the library shuts down.
Note:
Turn on the library power and repeat the steps above.
3 After the library has powered down, remove the hand restraint by completing the
following steps (see
figure
a
Remove the two thumb screws securing the hand restraint to the base of the
library.
b
Remove the hand restraint from the library.
Caution:
Avoid touching the printed circuit board.
Caution:
When removing the hand restraint, ensure that the robotics umbilical
cable is lying down in the correct position inside the platform and not
across the robotics track.
Installing the Library
23):
Scalar 50 Tape Library
25