Cable lengths and RFI performance
FC 30x
Filter
FC 301
With A2 filter
FC 302
FC 301
With A1/B
FC 302
With A1/B
FC 302
No RFI filter
In certain instances, shorten the motor cable to comply with EN 55011 A1 and EN 55011 B.
Copper (60/75°C) conductors recommended.
Control card performance:
Scan interval ........................................................................................ FC 301: 5 ms / FC 302: 1 ms
Control characteristics:
Resolution of output frequency at 0 - 1000 Hz ..................... FC 301: +/- 0.013 Hz / FC 302: +/- 0.003 Hz
Repeat accuracy of Precise start/stop (terminals 18, 19) ............ FC 301: ≤ ± 1ms / FC 302: ≤ ± 0.1 msec
System response time (terminals 18, 19, 27, 29, 32, 33) ...................
Speed control range (open loop) ............................................................... 1:100 of synchronous speed
Speed control range (closed loop) ............................................................ 1:1000 of synchronous speed
Speed accuracy (open loop) ................................................... 30 - 4000 rpm: Maximum error of ±8 rpm
Speed accuracy (closed loop) .............................................. 0 - 6000 rpm: Maximum error of ±0.15 rpm
All control characteristics are based on a 4-pole asynchronous motor
Surroundings:
Enclosure ≤ 7.5 kW ........................................................................................................ IP 20, IP 55
Enclosure ≥ 11 kW ......................................................................................................... IP 21, IP 55
Enclosure kit available ≤ 7.5 kW ........................................................................ IP21/TYPE 1/IP 4X top
Vibration test .......................................................................................................................... 1.0 g
Max. relative humidity ................... 5% - 95%(IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 721-3-3), uncoated .................................................................
Aggressive environment (IEC 721-3-3), coated ....................................................................
Ambient temperature ..................................................... Max. 50 °C (24-hour average maximum 45 °C)
Derating for high ambient temperature, see special conditions in the Design Guide
Minimum ambient temperature during full-scale operation ............................................................
Minimum ambient temperature at reduced performance ...........................................................
Temperature during storage/transport ......................................................................... -25 - +65/70 °C
Maximum altitude above sea level .......................................................................................... 1000 m
Derating for high altitude, see special conditions in the Design Guide
EMC standards, Emission ........................................................
EMC standards, Immunity ..................................................................... EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
See section on special conditions in the Design Guide
General Specifications
Supply voltage
200 - 240 V / 380 - 480 V /
380 - 500 V
200 - 240 V / 380 - 480 V
200 - 240 V / 380 - 500 V
550 - 600 V
MG.33.A5.02 - VLT is a registered Danfoss trademark
RFI compliance at max. motor cable lengths
<75 m. EN 55011 Group A2
<40 m. EN 55011 Group A1
<10 m. EN 55011 Group B
<150 m. EN 55011 Group A1
<40 m. EN 55011 Group B
Not compliant with EN 55011
FC 301: ≤ 10 ms / FC 302: ≤ 2 ms
EN 61800-3, EN 61000-6-3/4, EN 55011
class 3C2
class 3C3
0 °C
- 10 °C