Connecting The Refrigerant Piping; About Connecting The Refrigerant Piping; Precautions When Connecting The Refrigerant Piping - Daikin VRV 5 S Series Installer And User Manual

System air conditioner
Table of Contents

Advertisement

18.2 Connecting the refrigerant piping

18.2.1 About connecting the refrigerant piping

18.2.2 Precautions when connecting the refrigerant piping

RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1D – 2023.02
Refnet header
1~8 VRV DX indoor units
Before connecting the refrigerant piping
Make sure the outdoor and indoor units are mounted.
Typical workflow
Connecting the refrigerant piping involves:
Connecting the refrigerant piping to the outdoor unit
Connecting refrigerant branch kits
Connecting the refrigerant piping to the indoor units (see the installation manual
of the indoor units)
Insulating the refrigerant piping
Keeping in mind the guidelines for:
-
Pipe bending
-
Flaring pipe ends
-
Brazing
-
Using the stop valves
DANGER: RISK OF BURNING/SCALDING
NOTICE
NEVER install a drier to this unit to guarantee its lifetime. The drying material may
dissolve and damage the system.
NOTICE
Take the following precautions on refrigerant piping into account:
Avoid anything but the designated refrigerant to get mixed into the refrigerant
cycle (e.g. air).
Only use R32 when adding refrigerant.
Only use installation tools (e.g. manifold gauge set) that are exclusively used for
R32 installations to withstand the pressure and to prevent foreign materials (e.g.
mineral oils and moisture) from mixing into the system.
Protect the piping as described in the following table to prevent dirt, liquid or
dust from entering the piping.
Use caution when passing copper tubes through walls.
18
Piping installation
|
Installer and user reference guide
85

Advertisement

Table of Contents
loading

Table of Contents