9. Operating and Fault Indications

The two indicator lights (LED) on the front cover of PFU 2000/
PMU 2000 indicate pump operation (green) and/or fault (red).
Two external indicator lights (LED) can be connected instead of
the two indicator lights (LED) on the front cover.
The function of the indicator lights (LED) and the operating and
fault signal outputs appears from the table below.
The fault signal relay of the PMU 2000 will be deactivated for 15
minutes if any button has been pressed during the actual fault
condition and if "alarm suppression" "on" is selected (display
104).
Indicator Lights
Fault
Operation
(red)
(green)
Off
Off
Permanently
Off
on
Off
Flashing
Permanently
Off
on
Permanently
Permanently
on
on
Permanently
Flashing
on
28
Outputs PFU 2000
Fault
Operation
NO
NC
NO
NC
C
C
C NO NC
C NO NC
C NO NC
C
NO
NC
NO
NC
NO
NC
C
C
C NO NC
C
NO
NC
NO
NC
NO
NC
C
C
Outputs PMU 2000
Fault
Operation
NO
NC
NO
NC
C
C
NO
NC
C NO NC
C
C
NO
NC
C
NO
NC
C NO NC
NO
NC
C
C NO NC
C NO NC
C NO NC
NO
NC
C
Description
Electricity supply switched off
or supply failure.
At least one pump in each zone
is in operation.
All pumps in at least one zone
have been stopped:
· via external on/off switch or
via function selector in
PFU 2000 (pos. STOP),
· via PFU 2000/PMU 2000.
At least one pump is stopped
due to fault.
At least one pump is or has
been stopped due to fault.
At least one pump in each zone
is in operation.
All pumps in at least one zone
have been stopped:
· via external on/off switch or
via function selector in
PFU 2000 (pos. STOP),
· via PFU 2000/PMU 2000.
At least one pump is or has
been stopped due to fault.