8. Maintenance

8.1 Maintenance of Booster Set

8.1.1 Pumps

Before starting work on the pumps, make sure that
the electricity supply has been switched off and that it
cannot be accidentally switched on.
Pump bearings and shaft seal are maintenance-free.
If the pump is to be drained for a long period of inactivity, remove
one of the coupling guards to inject a few drops of silicone oil on
the shaft between the pump head and the coupling. This will pre-
vent the shaft seal faces from sticking.

8.1.2 Motor Bearings

Motors which are not fitted with grease nipples are maintenance-
free.
Motors fitted with grease nipples should be lubricated with a high-
temperature lithium-based grease, see the instructions on the fan
cover of GRUNDFOS motors.
In the case of seasonal operation (motor is idle for more than 6
months of the year), it is recommended to grease the motor when
the pump is taken out of operation.

8.1.3 Frost Protection

Pumps which are not being used during periods of frost should be
drained to avoid damage.
Drain the pump by loosening the vent screw in the pump head
and by removing the drain plug from the base.
Care must be taken to ensure that the escaping wa-
ter does not cause injury to persons or damage to the
motor or other components. In hot water installations,
special attention should be paid to the risk of injury
caused by scalding hot water.
Do not tighten the vent screw and replace the drain plug until the
pump is to be used again.

8.2 Maintenance of the Control 2000 S

The Control 2000 S is maintenance-free. It must be kept clean
and dry.