11. Fault finding
11.1 Noise in the pump
Cause
There is air in the pump.
Inlet pressure is too low.
11.2 Noise in the system
Cause
There is air in the system.
Differential pressure is too high.
11.3 Pump is not running, no power supply
Cause
System is switched off.
A fuse in the installation is blown.
Power supply failure.
11.4 Pump is not running, normal power supply
Cause
Controller is switched off.
Pump is blocked by impurities.
Pump is defective.
11.5 Insufficient flow
Cause
Pump performance is too low.
Hydraulic system is closed or system pressure is insufficient.
11.6 Pump runs at maximum speed and cannot be controlled
Cause
No signal from signal cable.
11.7 Fault indication on the operating panel
When an alarm is active, the LEDs indicate the alarm type as defined in the table below.
If multiple alarms are active at the same time, the LEDs only show the error with the highest priority. The priority is defined by the sequence of
the table.
Operating panel
LED1
LED2
red
green
●
●
●
Related information
5.2.1 Reduced supply voltage
7.2.2 Alarm status
LED3
LED4
yellow
yellow
yellow
●
●
Remedy
•
Let the pump run. The pump vents itself over time.
•
Increase the system pressure or check the air volume in the
expansion tank, if installed.
Remedy
•
Vent the system.
•
Reduce the pump performance at the pump or external controller.
Remedy
•
Check the system controller.
•
Replace the fuse.
•
Check the power supply.
Remedy
•
Check the controller and its settings.
•
Remove impurities. Deblock the pump from the front of the control
box with a screwdriver.
•
Replace the pump.
Remedy
•
Check the external controller and the pump settings.
•
Check the non-return valve and filter. Increase the system
pressure.
Remedy
•
Check if the cable is connected to the controller. If it is, replace the
cable.
LED5
Indication
●
Rotor is blocked.
Supply voltage too
low.
Electrical error.
Pump operation
Counter action
Trying to start again
Wait or deblock the
every 1.33 seconds.
shaft.
Only warning, pump
Control the supply
runs.
voltage.
Pump is stopped be-
Control the supply
cause of low supply
voltage.
voltage or serious fail-
Replace the pump.
ure.
19