17: External output isolation transformer connection
dI S
18: Display setting for autonomy time
Vac
19: Acceptable input voltage range setting
Vac
HLS
3 00
INPUT
00: Exit setting
ESC
Parameter 2: Allow or disallow external
output isolation transformer connection.
ENA: If selected, it's allowed to connect to
an external output isolation transformer.
DIS: If selected, it's not allowed to connect
to external output isolation transformer.
(Default)
Parameter 2: Set up the display setting for
autonomy time
EAT: If EAT is selected, it will display the
remaining autonomy time. (Default)
RAT: If RAT is selected, it will show
accumulated autonomy time so far.
Parameter 2: Set the acceptable high
voltage point and acceptable low voltage
point for input voltage range by pressing the
Down key or Up key.
HLS: Input high voltage point
280/290/300: setting the high voltage point
in parameter 2. (Default: 300Vac)
LLS: Bypass low voltage point
110/120/130/140/150/160: setting the
low voltage point in parameter 2. (Default:
110Vac)
Exit the setting mode.