07: Bypass voltage range setting
HLS
26 0
INPUT
08: Bypass frequency range setting
HLS
53 0
Hz
INPUT
09: Programmable outlets enable/disable
d I S
P1
22
Parameter 2: Set the acceptable high voltage
point and acceptable low voltage point for
Bypass mode by pressing the Down key or
Up key.
HLS: Bypass high voltage point
Vac
230-264: setting the high voltage point in
parameter 3 from 230Vac to 264Vac. (Default:
264Vac)
LLS: Bypass low voltage point
170-220: setting the low voltage point in
parameter 3 from 170Vac to 220Vac. (Default:
170Vac)
Parameter 2: Set the acceptable high fre-
quency point and acceptable low frequency
point for Bypass mode by pressing the
Down key or Up key.
HLS: Bypass high frequency point
51-55Hz: setting the frequency high loss
point from 51Hz to 55HZ(Default: 53.0Hz).
LLS: Bypass low Frequency point
45-49Hz: setting the frequency low loss point
from 45Hz to 49HZ(Default: 47.0Hz)
Parameter 2: Enable or disable the program-
mable outlets function.
You may choose the following two options:
ENA: Programmable outlets enable
DIS: Programmable outlets disable (Default)