5.5 UPS settings
2
NOTE!
Most parameters can be set only in bypass/standby mode; please set the UPS
to bypass/standby mode (see section 5.1) and then change parameters.
There are two parameters to set up the UPS.
Parameter 1:
Parameter 2&3:
Interface
01: Output voltage settings
23 0
OUTPUT
02: Frequency Converter enable/disable
CF ENA
20
1
888 888
For program alternatives. Refer to the table below.
The settings options or values for each program.
Settings
Parameter 2: Output voltage:
200: presents output voltage is 200Vac
208: present output voltage is 208Vac
220: present output voltage is 220Vac
Vac
230: present output voltage is 230Vac
240: present output voltage is 240Vac
NOTE:
Derate capacity to 80% when the output
voltage is adjusted to 200VAC/208VAC.
Parameter 2: Enable or disable converter
mode.
You may choose the following two options:
CF ENA: converter mode enable
CF DIS: converter mode disable (Default)
NOTE:
Derate capacity to 80% when Frequency
Converter mode is enabled.
3