Njoy UPCMCOP130HBAAZ01B User Manual page 23

Table of Contents

Advertisement

Available languages

Available languages

10: Programmable outlets setting
M
999
P1
11: Autonomy limitation setting
M
999
12: Battery total AH setting
bAH
7
13: Maximum charger current setting
CHA
Parameter 2: Set up backup time limits for
programmable outlets.
0-999: setting the backup time limits in
minutes from 0-999 for programmable
outlets which connect to non-critical
devices on battery mode. (Default: 999).
Parameter 2: Set up backup time on battery
mode for general outlets.
0-999: setting the backup time in minutes from
0-999 for general outlets on batt. mode.
DIS: Disable the autonomy limitation and
the backup time will depend on battery
capacity. (Default)
NOTE:
When setting as "0", the backup time
will be only 10 seconds.
Parameter 2: Set up the battery total AH of
the UPS.
7-999: setting the battery total capacity
from 7-999 in AH. Please set the correct
battery total capacity if external battery
bank is connected.
EXAMPLE: if you use Balder 1500 together
with one battery cabinet with 6 pcs of
HR09122F batteries (two strings of 3
batteries), total battery AH setting will
be: 9AH (UPS battery string capacity) +
2xHR09122F (2 strings of HR09122F
batteries inside battery cabinet) = 23AH
If you use external battery pack please set
the appropriate charging current based
on battery capacity used. Please use the
following table as reference:
23