4.4.2. Relay Function (FUNCTION)
Handheld
programmer
Options
4.4.3. Relay NO/NC (NC/NO)
Handheld programmer
Options
4.4.4. Relay State (STATE)
Handheld programmer
Options
6. Maintenance Settings (MAINT SET)
Use these parameters to set up schedules for calibration and maintenance. The device
will track itself based on operating hours, instead of a calendar-based schedule, and will
monitor its predicted lifetime.
The maintenance warnings and alarms are communicated to the end user through either
the status or condensed status bytes. This information can be integrated into any Asset
Management system. For optimal use, we recommend that you use SIMATIC PCS7 Asset
Management Software in conjunction with SIMATIC PDM.
6.1. Remaining Device Lifetime (DVC REMLIF)
Performing a reset to Factory Defaults will reset all Maintenance
Note:
parameters to their factory defaults.
The Remaining Device/Sensor Lifetime parameters set up schedules for calibration
and maintenance.
A5E42035355
DISABLED
MANUAL
LO ALM
HI ALM
ANY ALARM
FAILSAFE
NO
NC
OFF *
ON
SITRANS LR460 – INSTRUCTION MANUAL
* Relay is disabled and will not trigger
Relay state can be changed (using
4.4.4. Relay State (STATE)
parameter
Relay triggers when corresponding AIFB
goes below low alarm
Relay triggers when corresponding AIFB
goes above high alarm
Relay triggers when corresponding AIFB
goes below low alarm or above high alarm
Relay triggers when corresponding AIFB
goes to failsafe mode
*
Normally Open
Normally Closed
Relay de-energized
Relay energized
.