4.1.7.1.
Defines the operational lower range value of the output value in
engineering units.
Values
4.1.7.2.
Defines the operational upper range value of the output value in
engineering units.
Values
4.1.8. Output Limits (OUT. LIM.)
4.1.8.1.
The setting for the lower alarm limit in engineering units.
Values
4.1.8.2.
The setting for the lower warning limit in engineering units.
Values
4.1.8.3.
The setting for the upper warning limit in engineering units.
Values
4.1.8.4.
The setting for the upper alarm limit in engineering units.
Values
Page 72
Lower Value (LOWR VALUE)
Range: -999999 to 999999 m
Default: 0 m
Upper Value (UPPR VALUE)
Range: -999999 to 999999 m
Default: 70 m
Lower Limit Alarm (LO ALARM)
Range: -999 to 999 m
Default: -999 m
Lower Limit Warning (LO WARN) (PROFIBUS PA only)
Range: -999 to 999 m
Default: -999 m
Upper Limit Warning (UP WARN) (PROFIBUS PA only)
Range: -999 to 999 m
Default: 999 m
Upper Limit Alarm (UP ALARM)
Range: -999 to 999 m
Default: 999 m
SITRANS LR460 – INSTRUCTION MANUAL
A5E42035355