3.3.4. High Calibration Pt. (CAL HIGH)
Distance from Sensor Reference to High Calibration Point (corresponding to
High Level Point). Unit is defined in Sensor units.
Values
3.3.5. Unit (Level) (LVL UNIT)
Selected engineering units for Level (PV), referenced from Low Level Point (plus
level offset, if any).
Options
3.3.6. Level empty (PA); Low Level Point (HART) (LV MIN)
The level when the material is at Low Calibration Point. The unit is defined in
Level units.
Values
3.3.7. Level full (PA); High Level Point (HART) (UV MAX)
The level when the material is at High Calibration Point. The unit is defined in
Level units.
Values
3.3.8. Level Offset (LEV OFFSET)
A constant offset that can be added to Level to form PV/SV1 (default level
output). See page 133 for an illustration. The unit is defined in Level units.
Values
3.3.9. Sensor Offset (SEN OFFSET)
The offset from the Sensor's reference point to the vessel's reference point.
This is a constant offset that is added to the Sensor value. The unit is defined in
Sensor Units. (See How the Level Transducer Block works: on page 132 for
further details.)
Compensates, for example if the sensor head is changed.
Values
A5E42035355
Range: 0 to 100 m
Default: 0 m
%
percent
M, IN, CM, MM, FT, IN, M3, L, HL, IN3, FT3, YD3, GAL,
linear
IGAL, BUSH, BBL, BBL (LIQ)
%
default:
Range: -999999 to 999999 %
Default: 0 %
Range: -999999 to 999999 %
Default: 100 %
Range: -999999 to 999999 %
Default: 0 %
Range: -999999 to 999999 m
Default: 0 m