webConfig tool – Remote maintenance
• The "Address Link Label" can be removed from the device and affixed in the installation and layout dia-
grams to designate the device.
• Once it is affixed in the documents, the "Address Link Label" establishes a unique reference between
the mounting location, the MAC address or the device, and the associated control program.
There is no need for time-consuming searching, reading, and manually writing down of the MAC ad-
dresses of every device that is installed in the system.
NOTICE
Each device with Ethernet interface is uniquely identified via the MAC address assigned during
production.
The MAC address is also listed on the name plate of the device.
If multiple devices are commissioned in a system, the MAC address of each installed device
must be correctly assigned, e.g., during programming of the control.
Ä Remove the "Address Link Label" from the device.
Ä If necessary, add the IP address and the device name to the "Address Link Label".
Ä Affix the "Address Link Label" in the documents, e.g., in the installation diagram, according to the posi-
tion of the device.
8.2.3

IP addresses

IP addresses preset ex works (default IP address):
• Devices with "Frequency F3": 192.168.60.101
Devices with "Frequency F3" can also be identified by the part number code DDLS 5XX ... 3 ....
• Devices with "Frequency F4": 192.168.60.102
Devices with "Frequency F4" can also be identified by the part number code DDLS 5XX ... 4 ....
Reset IP address to factory setting
If the assigned IP address is no longer known by the user, the device can be reset to the default IP address
and default Subnet Mask.
Ä Switch off the voltage supply of the device.
Ä Switch the voltage supply back on again, and press the operating mode selector switch [MODE] at the
same time.
Ä Hold the operating mode selector switch [MODE] down until the device is ready.
ð The AUT LED flashes during the startup phase.
ð When the device is ready, the AUT LED illuminates continuously.
Ä When the LED AUT illuminates continuously, release the operating mode selector switch [MODE].
ð The device is reset to the factory set default IP address and standard Subnet Mask.