Adey MagnaClean CMX MIDI PRO ASSIST Installation And Servicing page 18

Sidestream monitored filtration
Table of Contents

Advertisement

Warning
Conditions for Trigger
Pump Fail
Current Sense
Parameter = Y
Pump Activated
Current level below
125mA
Service
Actual date beyond
Interval
Service Date (Control
Alarm
will not clear error
until new service date
entered)
Magnet-Only
Magnet-only service
Service
requirement value has
Warning*
been reached
Pressure
Pressure Differential
Differential
Warning value has been
Warning
reached
Pressure
Pressure Differential
Differential
Alarm value has been
Alarm
reached (Control will
not clear error until new
service date entered)
Low Flow
Low flow warning value
Warning
has been reached
Low Flow
Low flow alarm value
Alarm
has been reached
Low
Low temperature alarm
Temperature
value reached
Alarm
High
High temperature alarm
Temperature
value reached
Alarm
*NOTE: When the "Magnet-Only Service Warning" alarm is activated, the alarm is a service reminder
only which can be reset by holding down the MUTE button for 5 seconds. When the alarm is reset
via the mute button, the alarm will reinstate the previous Parameter 2 & 3 values, e.g. if Parameter 2
is set to "Weekly" the controller will provide another warning alarm in 2 weeks until/unless default
parameters are manually updated/changed.
18
Scrolled Message "Auto Reset" "Action on Outputs"
Pump Fail
Filter Service
Required
Magnet-Only
Service Warning
- Hold MUTE for 5
secs to reset
Differential
Pressure Warning
- Check Cartridge
Filter Service
Required
Low Flow Warning
Low Flow Alarm
Low Temperature
Warning
High Temperature
Warning
Pump – OFF
Buzzer – ON
LED Light – ON
N
Common Alarm – ON
Pump – ON
Buzzer – ON
N
LED Light – ON
Common Alarm – ON
Pump – ON
Buzzer – ON
N
LED Light – ON
Common Alarm – OFF
Pump – ON
Buzzer – ON
Y
LED Light – ON
Common Alarm – OFF
Pump – OFF
Buzzer – ON
LED Light – ON
N
Common Alarm – ON
Pump - ON
Buzzer - ON
LED Light - ON
Y
Common Alarm - OFF
Pump - OFF
Buzzer - ON
LED Light - ON
Y
Common Alarm - ON
Pump – ON
Buzzer – ON
Y
LED Light – ON
Common Alarm – ON
Pump – ON
Buzzer – ON
Y
LED Light – ON
Common Alarm – ON