PARAMETER PROGRAMMING MODE - ENGINEERS PARAMETER MENU (Code: 315)
Parameter
#
Service Date
-
Last Service Date Automatically updates when a new service date
-
Cartridge*
1
Present
Magnet Only**
2
Service Warning
Magnet Only
3
Service Warning
Duration
Pressure
4
Difference
Warning
Pressure
Difference Alarm
5
Flow Monitoring
6
Enable
7
Low Flow Warning Low Flow warning value
8
Low Flow Alarm
Sensor Minimum
9
Pressure
Sensor Maximum
10
Pressure
Temperature
11
Alarm Enable
Low Temperature
12
Alarm
High Temperature
13
Alarm
Pump Required
14
Current Sense
15
Alarm Relay
16
Contact
17
ID Number
Pump Hours
18
Battery Activation Enable or disable the Battery (Maintains date and
19
Description
Adjust future service date: Day/Month/Year. Press
& hold 'SET to cycle across values. Will pass onto
next parameter once complete
has been entered and will be visible next time user
accesses parameters
Monitors presence of a filter cartridge
Daily/weekly/monthly warning alarm
Number of days/weeks/months (unit representation
dependent upon Parameter 2 Alarm choice - Daily,
Weekly or Monthly)
Warning trigger point based on pressure
differential output (The default value of 0.4 bar
should not be changed)
Alarm trigger point based on pressure differential
output (The default value of 0.6 bar should not be
changed)
Enables/disables flow monitoring & measurement
Low Flow alarm value
Maximum pressure value of sensor (The default
value of 0.0 bar should not be changed)
Maximum pressure value of sensor (The default
value of 2.5 bar should not be changed)
Enables/disables temperature alarm
Low temperature alarm value
High temperature alarm value
Disables activation of pump relay. If set to NO, Current
Sense (Parameter 13) will auto NO; When set to YES,
Current Sense (Parameter 13) will auto YES
Monitors current for presence of pump
Type of Contact for Alarm Output (NO= Relay in
open position; closes on alarm; NC = Relay in closed
position; opens on alarm)
Address for Mod Bus
Total Operation Hours for Pump (Auto Update)
time settings if power is lost to the controller - on
first power up battery will automatically activate)
Default
Range
-
-
-
-
No
Yes/No
Daily
Daily
Weekly
Monthly
2
1-12
0.4
0.1 - 2.5 bar
0.6
0.1 - 2.5 bar
Y
Y/N
10
0 - 200L
0
0 - 200L
0.0 bar
0 - 2.5 bar
2.5 bar
0 - 2.5 bar
Yes
Yes/No
4°C
0 - 120°C
90°C
0 - 120°C
Yes
Yes/No
Yes
Yes/No
No
No/NC
0
0 - 99
0 - 999
1 = 24 hrs
No
Yes/No