3. SIGNALS AND WIRING
(2) Switch connection (not executing a test pulse diagnosis)
Wire without using PLSA and PLSB.
(Test pulse diagnosis disabled)
(3) Switch connection (executing a test pulse diagnosis)
The pulses for diagnosis will output from PLSA and PLSB. Wire so that the pulse signals outputted from
PLSA and PLSB pass through the switch.
Switch
Switch
(Test pulse diagnosis disabled)
CN10A
24 V DC ± 10%
0.8 A
DICOMA
DI1A, etc.
24 V DC ± 10%
CN10B
0.8 A
DICOMB
DI1B, etc.
24 V DC ± 10%
0.8 A
24 V DC ± 10%
0.8 A
3 - 8
MR-D30
Approx. 5.6 kΩ
Approx. 5.6 kΩ
MR-D30
CN10A
DC24VA
PLSA
DICOMA
DI1A, etc.
Approx. 5.6 kΩ
CN10B
DC24VB
PLSB
DICOMB
DI1B, etc.
Approx. 5.6 kΩ