2. INSTALLATION
(b) Installation of two or more servo amplifiers
Leave a large clearance between the top of the servo amplifier and the cabinet walls, and install a
cooling fan to prevent the internal temperature of the cabinet from exceeding the environment.
When mounting the servo amplifiers closely, leave a clearance of 1 mm between the adjacent servo
amplifiers in consideration of mounting tolerances. In this case, keep the ambient temperature within
0 ˚C to 45 ˚C or use the servo amplifier with 75% or less of the effective load ratio.
Cabinet
100 mm or more
30 mm
or more
40 mm or more
(Note 1)
Leaving clearance
Note 1. For the 11 kW to 22 kW servo amplifiers, the clearance between the bottom and the ground will be 120 mm or more.
2. When you install MR-J4-500_-RJ on the right side, the clearance between the left side and the wall will be 25 mm or more.
(2) Others
When using heat generating equipment such as the regenerative option, install them with full
consideration of heat generation so that the servo amplifier is not affected.
Install the servo amplifier on a perpendicular wall in the correct vertical direction.
POINT
Close mounting is possible depending on the capacity of the servo amplifier.
Refer to section 1.3.1 of "MR-J4-_B(-RJ) Servo Amplifier Instruction Manual" or
section 1.3 of "MR-J4-_A(-RJ) Servo Amplifier Instruction Manual" for
possible/impossible of close mounting.
When mounting the servo amplifiers closely, do not install the servo amplifier
whose depth is larger than that of the left side servo amplifier since CNP1,
CNP2, and CNP3 connectors cannot be disconnected.
10 mm or more
(Note 2)
30 mm
or more
Cabinet
1 mm
Mounting closely
2 - 3
100 mm or more
1 mm
40 mm or more
30 mm
or more
Top
Bottom