How Do I Change The Profibus Address Of The Com Unit - Pepperl+Fuchs LB8 09 Series Getting Started

Remote i/o stations with com unit
Table of Contents

Advertisement

GETTING STARTED
Integrating Remote I/O Stations with Com Unit LB/FB8X09* / LB/FB8X05*

6.2. How Do I Change the PROFIBUS Address of the Com Unit?

The current PROFIBUS address must be known to be able to change the PROFIBUS
address of the com unit when configuring via PROFIBUS (e.g., with Softing
PROFIusb). First, determine the PROFIBUS address of the com unit (section 6.1.).
Then change the PROFIBUS address as follows:
1.
on the PROFIdtm DPV1 Interface to establish a connection.
2.
on Interface → Additional Functions → Set Device Station Address
to change the PROFIBUS address:
Changes are not applied until "Store to
Device" is selected
When configuring via the service bus interface (e.g., with ICPCON), the PROFIBUS
address can be changed directly via:
Com unit → Parameter → Parameterization → Edit Device Data
(Offline):
Changes are not applied until "Store to Device" is selected
Specify the current address
Specify the desired address and then set
In contrast to a configuration via
PROFIBUS, the PROFIBUS address
can be changed via the service bus
in PACTware at this point.
32