GETTING STARTED
Integrating Remote I/O Stations with Com Unit LB/FB8X09* / LB/FB8X05*

5.5.2. Diagnostics via the Online View in the Simatic Manager

In order to be able to make good use of the following online view, the
PROFIBUS slave must first be configured (see section 4. Configuration of
the PROFIBUS Slave).
The
button can be used to switch between the online and the offline view.
1. Switch to the online view to detect any errors.
The following error images frequently appear here:
Module not available:
Check whether the PROFIBUS address in the HW Config matches the
PROFIBUS address of the com unit and the specification of the PROFIBUS
address in PACTware.
Error:
If nothing is connected and the line fault detection is not disabled, this error
could indicate a line breakage.
2.
on Node → Module Status to open the diagnostics page.
3. Open the 2nd tab "DP slave diagnostics", where a more detailed error
message is displayed.
30