LB Remote I/O System
Product Specifications
2.4.4

Backplane and Module Compatibility

In principle, LB backplanes are compatible with all LB modules. Single-width I/O modules
occupy one slot, while double-width I/O modules occupy two slots. However, please be aware
of the following restrictions.
Temporary Overload of the Power Supply
To avoid an overload of the power supply in the startup phase as a result of increased startup
currents, the number of certain I/O modules on the backplane is limited.
Use:
A maximum of 11 LB3*, LB4*, and LB7* single-channel I/O modules.
Each of these I/O modules consumes 9.09 % of the startup capacity.
Or a maximum of 8 LB3*and LB7* four-channel I/O modules.
Each of these I/O modules consumes 12.5 % of the startup capacity.
LB9035A
Only use this backplane with the following I/O modules:
Digital input: LB1*08*
Digital output: LB6005*, LB6006*, LB6*08*, LB6*10* ... LB6*15*
Analog input: LB3*05*, LB5*04*, LB5*05*
Analog output: LB4*05*
2.4.5

Scope of Delivery

Base backplanes are not delivered with any accessories.
Extension backplanes are delivered with a 1-m-long double-ended cordset (LB9140A). The
double-ended cordset establishes the connection to the base backplane.
2.5

I/O Modules, Com Units, and Power Supplies

2.5.1

Function

I/O modules are signal conditioning devices. Field signals from a hazardous area are
conditioned for controllers or process control systems in a safe area. The slots for the I/O
modules on the backplane have equal status, meaning functions can be arranged side by side
as required.
Com units form the interface between the I/O modules and the process control system. A com
unit can control up to 46 I/O modules and transfer their signals across various standard buses.
The com unit converts the protocol of the bus integrated in the backplane to the protocol of the
higher-level bus system.
Power supplies provide power to the I/O modules and the associated com units on a
backplane. The slots for com units are mechanically coded on the backplane and marked
accordingly.