5. START UP SEQUENCE.
Connect the inverter to the DC power supply only.
1.
Once the inverter display has turned on, follow the steps below to change the Modbus address of the device (only for systems with the
2.
485/WIFI 24H EQX2-T communication
From the main menu, press ENT X times, depending on the number of MPPTs in the unit, until you reach the "General Settings" menu.
c.
Press and hold for 3s to enter the next menu "System Info".
d.
Press ENT 13 times until you reach the "Modbus Address" menu, hold for 3s to enter it and access the numerical characters; press ENT
e.
repeatedly to increase each digit and set the desired address. To change between the digits press and hold ENT for 3s.
To navigate within the different menus, a short press (1s.) enables you to scroll through the screens of a given menu, while a long
press (3s.) allows access to the parameters or sub-screens of the selected menu.
Once the Modbus address has been changed, connect the AC power supply.
3.
Connect the automatic master circuit breaker (IGA) to re-establish the power supply to the whole installation.
Startup continues in the next section. Do not disconnect any device from the installation.
For further information, Annex II includes a table listing all the possible LED statuses of the 485/WIFI 24H EQX2-T communication module
with their respective descriptions for troubleshooting possible errors.