Address Description
40488
RS-485 response delay time in ms, valid range, 0
~ 30
Only for Modbus RTU protocol
40489
RS-485 host watchdog timeout value, 0 ~ 255, in
0.1s
Only for Modbus RTU protocol
40492
RS-485 host watchdog timeout count, write 0 to
clear
Only for Modbus RTU protocol
30513 ~
High latched analog input value of channel 0 to 1 R
30514
40513 ~
40514
30545 ~
Low latched analog input value of channel 0 to 1 R
30546
40545 ~
40546
30556
Module reset status, 1: power-on, 2: watchdog, 3:
40556
software reset command
Only for Modbus TCP protocol
40558
Ethernet host watchdog timeout value, 5 to 65535,
in second, 0 to disable.
Only for Modbus TCP protocol
30559
Ethernet host watchdog timeout count.
40559
Only for Modbus TCP protocol
30560
Module name, 0x0120
40560
Only for Modbus TCP protocol
40564
TCP disconnection timeout value, 5 to 65535, in
second, 0 to disable.
Only for Modbus TCP protocol
40565
Module reset timeout value, 30 to 65535, in
second, 0 to disable.
Only for Modbus TCP protocol
40865
RTC year, 2000 to 2159
40866
RTC month, 1 to 12
40867
RTC date, 1 to 31
DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual
Attribute
R/W
R/W
R/W
R
R/W
R
R
R/W
R/W
R/W
R/W
R/W
Version 1.1.3 Dec 2020 - 74 -