Address Description
30513 ~
High latched analog input value of channel 0 to 4 R
30517
40513 ~
40517
30545 ~
Low latched analog input value of channel 0 to 4 R
30549
40545 ~
40549
30556
Module reset status, 1: power-on, 2: watchdog, 3:
40556
software reset command
40558
Ethernet host watchdog timeout value, 5 to
65535, in second, 0 to disable.
30559
Ethernet host watchdog timeout count.
40559
30560
Module name, 0x0100
40560
40564
TCP disconnection timeout value, 5 to 65535, in
second, 0 to disable.
40565
Module reset timeout value, 30 to 65535, in
second, 0 to disable.
40801
Number of seconds in a cycle to display
temperature in Celsius on LCD, 0 ~ 100
40802
Number of seconds in a cycle to display
temperature in Fahrenheit on LCD, 0 ~ 100
40803
Number of seconds in a cycle to display relative
humidity on LCD, 0 ~ 100
40804
Number of seconds in a cycle to display date on
LCD, 0 ~ 100
40805
Number of seconds in a cycle to display time on
LCD, 0 ~ 100
40865
RTC year, 2000 to 2159
40866
RTC month, 1 to 12
40867
RTC date, 1 to 31
40868
RTC hour, 0 to 23
40869
RTC minute, 0 to 59
40870
RTC second, 0 to 59
40871
Total number of log records, low word
40872
Total number of log records, high word
DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual
Attribute
R
R/W
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R