ICPDAS DL-100-E User Manual

Illumination/temperature/humidity/dew point data logger
Table of Contents

Advertisement

Quick Links

DL-100-E/DL-101-E
DL-110-E/DL-120-E
Illumination/Temperature/Humidity/Dew Point
Data Logger User Manual
Version: 1.1.3
Date: Dec 2020
DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual
Version 1.1.3 Dec 2020 - 1 -

Advertisement

Table of Contents
loading

Summary of Contents for ICPDAS DL-100-E

  • Page 1 DL-100-E/DL-101-E DL-110-E/DL-120-E Illumination/Temperature/Humidity/Dew Point Data Logger User Manual Version: 1.1.3 Date: Dec 2020 DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 1 -...
  • Page 2 Copyright © 2018 by ICP DAS. All rights are reserved. Contact Us If you have any questions, feel free to contact us via email at: Service@icpdas.com DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 2 -...
  • Page 3: Table Of Contents

    Q1: How to set the Accessible IP? ..................53 Q2: How to delete the Accessible IP settings? ..............53 Q3: How to clear the data logged in a DL-100-E module? ..........54 Q4: How to download firmware into a DL-100-E module? ..........54 Appendix A: ModbusMasterToolPC ................
  • Page 4: Introduction

    1. Introduction The DL-100-E series are Data Logger devices that can be used to record illumination, temperature, humidity and dew point data, together with date and time stamp information. Up to 600,000 downloadable records can be stored. Real-time data can be...
  • Page 5 Features Built-in Web Server With the built-in Web server, users can easily log in to the DL-100-E series module via a standard web browser to monitor the data and configure the settings without install any software in the terminal. Get Real-time Data Anywhere and Anytime...
  • Page 6 Easy integration with SCADA software Modbus is one of the most popular protocols used in the industrial world. Supporting traditional serial protocols of Ethernet protocols allow the DL-100-E series module well-integrated into the HMI/SCADA systems. Easy Wiring Support for Ethernet and Power over Ethernet (PoE) interfaces for users to choose the appropriate one to meet the field requirements.
  • Page 7: Hardware

    MQTT Security Password and IP Filter Dual Watchdog Yes, Module (2.3 seconds), Communication (Programmable) System Real Time Clock Data Logger Yes, 600,000 Records DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 7 -...
  • Page 8 IP66 IP65 Installation DIN-Rail or Wall mounted Environment Operating Temperature -20 to +60°C Storage Temperature -30 to +80°C Humidity 5 to 95% RH, Non-condensing DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 8 -...
  • Page 9: Appearance

    2.2 Appearance DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 9 -...
  • Page 10 The Ethernet port can be used to connect to either a PoE switch or a non-PoE switch. Installing a waterproof attachment on an RJ45 connector. The DL-100-E series module is equipped with an RJ-45 waterproof connector that ensures the device is able to withstand potential contaminants in dusty environments.
  • Page 11 Sealing Nut Gasket Clamp Ring Seal Step 3: Wrap the Gasket around the Clamp Ring Step 4: Wrap the Lock Nut around the Clamp Ring DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 11 -...
  • Page 12 Step 7: Insert the RJ-45 Cable into the RJ-45 Connector Step 8: Push the RJ-45 waterproof connector assembly forward so that it covers the RJ-45 connector DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 12 -...
  • Page 13 Step 9: Connect the RJ-45 Cable to the COM Port on the DL-100-E module Step 10: Firmly tighten the connector to the module and ensure that it is completely connected. Connector for Power / Alarm Relay Output / RS-485 DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual...
  • Page 14 Step 2: Insert the conductors into the holes on the 5 Pin Cable Connector. See the figure below for the correct pin-out connections 5 Pin Cable Connector Step 3: Wrap the Lock Nut around the 5 Pin Cable Connector DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 14 -...
  • Page 15 Step 5: Wrap the Clamp Ring around the 5 Pin Cable Connector Step 6: Insert the Seal into the Clamp Ring Step 7: Push the Sealing Nut forward and Hand-tighten it to seal the assembly DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 15 -...
  • Page 16 The fool-proofing groove (as red circle) is useful for easy connection of power cable and power plug. Please make sure they are located in the same direction when connecting these two items. Relay Output Wire Connection (DL-101-E Only) DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 16 -...
  • Page 17: Dimensions (Unit: Mm)

    2.3 Dimensions (unit: mm) DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 17 -...
  • Page 18: Cabling For Power And Network

    2.4 Cabling for Power and Network Note  Do not install the DL-100-E series module near a vent, a ventilation fan or a door where the air flows faster.  Avoid installing in locations where the temperature is below -20°C or above 60°C.
  • Page 19 The iAir App from ICPDAS and the DL-300 Utility are able to search for loggers by broadcast, therefore only devices that exist on the same subnet can be searched for. This means that the Host PC, the Android device and the logger must have the same broadcast address.
  • Page 20: Configuration Via Web Browser

    3. Configuration via Web Browser The DL-100-E series logger has a built-in web server that provides simple web pages for remote monitoring real-time data and configuring the logger with a standard browser. For opening the web page in DL-100-E series module, the factory default IP address (192.168.255.1), Subnet Mask (255.255.0.0) and Gateway (192.168.0.1) need be set...
  • Page 21: Logging Into The Dl-100-E

    3.2 Logging into the DL-100-E 1. Enter the IP address for your DL-100-E in the address bar of a web browser. 2. Type the Login password, and click the Submit button. (The default Login password is Admin, case sensitive.) DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual...
  • Page 22: Home

    3.3 Home The first page displayed is Home, it shows the based configuration of the DL-100-E module and the real-time data as below: In the Sensor Readings field is the real-time data of temperature, humidity, dew point and ambient light, the minimum value (Low Latched) and maximum value (High Latched) logged.
  • Page 23: Network

    IP/Subnet Mask/Gateway addresses, the port number and the NetID for Modbus TCP communication. Remember to click on the Update Settings button to update new parameters. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 23 -...
  • Page 24 EtherIO maximum length is 18 characters. The Reboot button is used to reboot the DL-100-E. After pressing the button, a user needs to login the DL-100-E logger again to using the web interface. The Restore Defaults button can be used to restore the following settings to factory DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 24 -...
  • Page 25: Mqtt

    EtherIO Accessible IP Disabled The Update button is used to update firmware for DL-100-E. For details regarding firmware update, please refer to the section 7. FAQ Q4. 3.5 MQTT MQTT stands for MQ Telemetry Transport, it is a publish/subscribe, extremely simple and lightweight messaging protocol, designed for constrained devices and low-bandwidth, high-latency or unreliable networks.
  • Page 26 / Ambient Light (LUX) Sub Topic Name: sets the sub topic name for each item. A MQTT client subscribes the messages form a MQTT broker by specifying the topic name as DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 26 -...
  • Page 27 If a MQTT message is published to topic name: “Module Topic Name + Message Attribute Sub Topic Name” for a DL-100-E logger, the logger will follow the MQTT message described to set the attribute for displaying a message on the screen.
  • Page 28: I/O Settings

    Sets the High alarm limit conditions for Relative Humidity/ Limit Temperature/ Dew Point. Beep On Enable/disable beep on alarm for Temp /RH /Dew point Alarm DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 28 -...
  • Page 29 Safe value. The settings for Power On Value and Safe Value are unavailable when any one setting in the Alarm Mode is enabled All the settings take effect after clicking the Update Settings button. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 29 -...
  • Page 30 In this table it shows the settings for data logger. All the settings take effect after clicking the Update Settings button. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 30 -...
  • Page 31 Start Period End Sets the stop time for Period mode Note that all settings will take effect immediately after clicking the Update Settings button. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 31 -...
  • Page 32: Filter Ip

    3.7 Filter IP For limiting the devices to access the DL-100-E logger, users can specifies particular devices by setting their IP addresses on this page. When the addresses are 0.0.0.0 from IP1 to IP5, all the devices can access the logger. Once any of the 5 IP address columns is set, only the device with which IP is saved in the list can assess the logger.
  • Page 33: Monitor

    3.8 Monitor It lists the IP of the devices which are connected to the DL-100-E module. 3.9 Change Password On this page users can change the passwords for login the logger and locking the touch screen. The factory default for the DL-100-E touch screen has no password protection.
  • Page 34: Logout

    3.10 Logout Click the Logout on any page to logout the DL-100-E. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 34 -...
  • Page 35: Configuration Via Rs-485(Dl-110-E / Dl-120-E Only)

    4.1. Building the RS-485 Connection 1. Download the DCON Utility Pro from http://ftp.icpdas.com/pub/cd/iiot/utility/dcon_utility_pro/ 2. Launch the DCON_Utility_Pro.exe. Stop Search Start Search Set COM port Configuration DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 35 -...
  • Page 36 COM port. 4. Select the COM Port number used to connect the DL-110-E logger. 5. The Baud Rate is factory default to 9600 bps. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 36 -...
  • Page 37 6. Select the Protocol tab and check the protocol that set in the logger. 7. Select the Format tab and check the parity that set in the logger. 8. Click the Start Search icon. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 37 -...
  • Page 38 ON position and power cycle the logger, then the item can be modified. After complete setting, set the pin 4.INIT back to OFF position and power cycle the logger again to take the setting effect. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 38 -...
  • Page 39: Ai Tab

    Adjust the Ambient Light Ambient Light Humidity offset Temperature and Adjust the temperature Adjust the humidity offset offset Dew point temperature (°C) DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 39 -...
  • Page 40: Logger Configuration

    In the Data Logger form, you can change the data logger related settings. Click on the Apply button to save the changes to the module. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 40 -...
  • Page 41: Monitoring Via Mobile Devices

    IP address, or by performing an automatic search for available devices. If a DL-100-E series module cannot be searched in the iAir App, please contact with the network administrator to make sure the module and your mobile devices are addressed on the same sub-network.
  • Page 42: Utility To Get/Manage Data Log

    6. Utility to Get/Manage Data Log DL-300 Utility is a convenient, easy-to-use management utility running on Windows platform that allows users to monitor the real-time data and trend chart from DL-100-E series modules on the Ethernet, it can group the DL-100-E series modules for group view management, log alarm events with timestamp, download the logged data from a DL-100-E series logger and export the data to *.csv files for performing statistical...
  • Page 43 3-2. Click the Search New Device button to search the DL-100-E modules connected on the same Ethernet network. 3-3. Check the checkbox next to a module and click the Add button to add the module in the utility. 3-4. Highlight a module and click the Edit Device button to configure the module.
  • Page 44 4. Get real-time data, trend chart and alarm event. 4-1. Click the List icon to obtain the real-time data. It also lists the connect status, group information and IP address for every DL-100-E logger. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual...
  • Page 45 Temperature or Humidity to access the trend chart for those real-time data, check the checkbox next to each DL-100-E logger to display its trend chart or uncheck it to cancel display. Drag and drop the trend chart can move it to see the data not be displayed in the chart.
  • Page 46 Check the checkbox next to The Record Time Everyday can schedule auto generate report everyday at the time set in the dropdown menu. Click on the OK button to complete the settings. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 46 -...
  • Page 47 5. Download data in a DL-300 logger and export the data 5.1. Select Update Database on the Settings menu 5.2. Click the Start button to download the data in DL-100-E modules. 5.3. Click the close icon to exit the download procedure when all data are downloaded.
  • Page 48 5.5. Highlight the desired module, set the Start Time and End Time, and then click the Search button. The data in the time period will be listed as below. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 48 -...
  • Page 49 5.6. Click the Export button to export the searched data in *.csv files for performing statistical analysis in Excel. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 49 -...
  • Page 50 6.2 Click the New button, enter the group name and click the OK button in the pop-up box, and then click the OK button in the Group Settings box. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 50 -...
  • Page 51 Edit Device button, select the group name for the module and click the OK button in the pop-up Device Property box to complete the setting. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 51 -...
  • Page 52 6-4. Monitor the group data by clicking the Group icon and then highlighting the group name. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 52 -...
  • Page 53: Faq

    IP setting and use after repowering. Once any of those in the list is set, only the device for which the IP address is saved in the list can assess the DL-100-E. Q2: How to delete the Accessible IP settings?
  • Page 54: Q3: How To Clear The Data Logged In A Dl-100-E Module

    Ethernet network may not function correctly. Step 1: Download and Install the eSearch Utility (version is v1.1.14 or later) on your Host PC, and then run the Utility to search for DL-100-E modules connected to the network.
  • Page 55 Right click on the DL-100-E module name then select Firmware Update. Select the firmware file and click on the Open button. Make sure the IP address and MAC address are correct. Click on the OK button. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual...
  • Page 56 A command prompt window will be displayed to show the progress. Log in the DL-100-E web page. Click on the Network tab then click on the Update button. When it shows “% Complete: 100%”, the update is finished. You can close the command prompt window.
  • Page 57 DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 57 -...
  • Page 58: Appendix A: Modbusmastertoolpc

    DL-100-E logger. 1. Launch the ModbusMasterToolPC.exe. 2. Select New in the File menu. 3. Input the file name and click on the Save button. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 58 -...
  • Page 59 4. Select Connect in the Connection menu. 5. Select the communication interface. When using TCP/IP as the interface, input the IP for your logger and click on the OK button. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 59 -...
  • Page 60 6. Select Definition in the Setup menu. 7. Select the Modbus Function code, input the start address and length, and click on the OK button. 8. Read data. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 60 -...
  • Page 61 DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 61 -...
  • Page 62: Appendix B: Modbus Address Table

    Module reset status, 1: power-on, 2: watchdog, 40556 3: software reset command 40558 Ethernet host watchdog timeout value, 5 to 65535, in second, 0 to disable. DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 62 -...
  • Page 63 Hour of the data logger sampling period, 0 ~ 24 R/W 40879 Minute of the data logger sampling period, 0 ~ 40880 Second of the data logger sampling period, 0 ~ DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 63 -...
  • Page 64 00389 value of channel 0 to 4 00417 ~ Write 1 to clear low latched analog input 00421 value of channel 0 to 4 DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 64 -...
  • Page 65: B-2. Dl-101-E Modbus Address Mappings (Base 1)

    Temperature offset in 0.01°C 40481 Firmware version (low word) 40482 Firmware version (high word) 40483 Module name (low word), 0x0100 40484 Module name (high word), 0x444C DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 65 -...
  • Page 66 RTC minute, 0 to 59 40870 RTC second, 0 to 59 40871 Total number of log records, low word 40872 Total number of log records, high word DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 66 -...
  • Page 67 Ending hour when logging in period mode, 0 ~ 23 R/W 40891 Ending minute when logging in period mode, 0 ~ 40892 Ending second when logging in period mode, 0 ~ DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 67 -...
  • Page 68 Write 1 to clear high latched analog input value of 00389 channel 0 to 4 00417 ~ Write 1 to clear low latched analog input value of 00421 channel 0 to 4 DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 68 -...
  • Page 69: B-3. Dl-110-E Modbus Address Mappings (Base 1)

    40483 Module name (low word), 0x0100 40484 Module name (high word), 0x444C 40485 RS-485 module address, 1 to 247 Only for Modbus RTU protocol DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 69 -...
  • Page 70 Only for Modbus TCP protocol 30559 Ethernet host watchdog timeout count. 40559 Only for Modbus TCP protocol 30560 Module name, 0x0110 40560 Only for Modbus TCP protocol DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 70 -...
  • Page 71: The Starting Record To Read Log Data, Low Word R/W

    Starting date when logging in period mode, 1 ~ 31 R/W 40884 Starting hour when logging in period mode, 0 ~ 23 R/W 40885 Starting minute when logging in period mode, 0 ~ DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 71 -...
  • Page 72: Starting Second When Logging In Period Mode, 0 ~ R/W

    Write 1 to clear high latched analog input value of 00391 channel 0 to 6 00417 ~ Write 1 to clear low latched analog input value of 00423 channel 0 to 6 DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 72 -...
  • Page 73: B-4. Dl-120-E Modbus Address Mappings (Base 1)

    01: no parity, 2 stop bit 10: even parity, 1 stop bit 11: odd parity , 1 stop bit Only for Modbus RTU protocol DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 73 -...
  • Page 74 0 to disable. Only for Modbus TCP protocol 40865 RTC year, 2000 to 2159 40866 RTC month, 1 to 12 40867 RTC date, 1 to 31 DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 74 -...
  • Page 75: Ending Date When Logging In Period Mode, 1 ~ 31 R/W Ending Hour When Logging In Period Mode, 0 ~ 23 R/W Ending Minute When Logging In Period Mode, 0 ~ R/W

    Ending hour when logging in period mode, 0 ~ 23 R/W 40891 Ending minute when logging in period mode, 0 ~ 40892 Ending second when logging in period mode, 0 ~ DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 75 -...
  • Page 76 Write 1 to clear high latched analog input value of 00386 channel 0 to 1 00417 ~ Write 1 to clear low latched analog input value of 00418 channel 0 to 1 DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 76 -...
  • Page 77: Revision History

    Added Modbus register 40181 module alias name Changed Modbus register 40181 module alias name to read 1.1.2 2019/May only 1.1.3 2020/Dec Fixed typos and reformatted DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020 - 77 -...

This manual is also suitable for:

Dl-101-eDl-110-eDl-120-e