B-3. Dl-110-E Modbus Address Mappings (Base 1) - ICPDAS DL-100-E User Manual

Illumination/temperature/humidity/dew point data logger
Table of Contents

Advertisement

B-3. DL-110-E Modbus Address Mappings (Base 1)

Address Description
30001 ~
Analog input value of channel 0 to 6. channel 0:
30007
relative humidity in 0.01%, channel 1: temperature
40001 ~
in 0.01°C, channel 2:temperature in 0.01°F,
40007
channel 3:
dew point temperature in 0.01°C, channel 4: dew
point temperature in 0.01°F, channel 5: low word
of ambient light in lux, channel 6: high word of
ambient light in lux
40181 ~
Module alias name
40196
40272
Modbus NetID
Only for Modbus TCP protocol
30301
Number of the digital input channels
40301
Only for Modbus TCP protocol
30311
Number of the digital output channels
40311
Only for Modbus TCP protocol
30321
Number of the analog input channels
40321
Only for Modbus TCP protocol
30331
Number of the analog output channels
40331
Only for Modbus TCP protocol
30352
Firmware version in hex format
40352
Only for Modbus TCP protocol
40449
Relative humidity offset in 0.01%
40450
Temperature offset in 0.01°C
40454
Ambient light offset in lux
40481
Firmware version (low word)
40482
Firmware version (high word)
40483
Module name (low word), 0x0100
40484
Module name (high word), 0x444C
40485
RS-485 module address, 1 to 247
Only for Modbus RTU protocol
DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual
Attribute
R
R
R/W
R
R
R
R
R
R/W
R/W
R/W
R
R
R
R
R/W
Version 1.1.3 Dec 2020 - 69 -