Appendix B: Modbus Address Table

B-1. DL-100-E Modbus Address Mappings (Base 1)

Address Description
30001 ~
Analog input value of channel 0 to 4. channel 0:
30005
relative humidity in 0.01%, channel 1:
40001 ~
temperature in 0.01°C, channel 2:temperature
40005
in 0.01°F, channel 3: dew point temperature in
0.01°C, channel 4: dew point temperature in
0.01°F
40181 ~
Module alias name
40196
40272
Modbus NetID
30301
Number of the digital input channels
40301
30311
Number of the digital output channels
40311
30321
Number of the analog input channels
40321
30331
Number of the analog output channels
40331
30352
Firmware version in hex format
40352
40449
Relative humidity offset in 0.01%
40450
Temperature offset in 0.01°C
40481
Firmware version (low word)
40482
Firmware version (high word)
40483
Module name (low word), 0x0101
40484
Module name (high word), 0x444C
30513 ~
High latched analog input value of channel 0 to
30517
4
40513 ~
40517
30545 ~
Low latched analog input value of channel 0 to
30549
4
40545 ~
40549
30556
Module reset status, 1: power-on, 2: watchdog,
40556
3: software reset command
40558
Ethernet host watchdog timeout value, 5 to
65535, in second, 0 to disable.
DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual
Attribute
R
R
R/W
R
R
R
R
R
R/W
R/W
R
R
R
R
R
R
R
R/W
Version 1.1.3 Dec 2020 - 62 -