ICPDAS DL-100-E User Manual page 70

Illumination/temperature/humidity/dew point data logger
Table of Contents

Advertisement

Address Description
40486
RS-485 baud rate and parity settings
Bits 5:0
Baud rate, valid range: 3 ~ 10
Bits 7:6
00: no parity, 1 stop bit
01: no parity, 2 stop bit
10: even parity, 1 stop bit
11: odd parity , 1 stop bit
Only for Modbus RTU protocol
40488
RS-485 response delay time in ms, valid range, 0
~ 30
Only for Modbus RTU protocol
40489
RS-485 host watchdog timeout value, 0 ~ 255, in
0.1s
Only for Modbus RTU protocol
40492
RS-485 host watchdog timeout count, write 0 to
clear
Only for Modbus RTU protocol
30513 ~
High latched analog input value of channel 0 to 6 R
30519
40513 ~
40519
30545 ~
Low latched analog input value of channel 0 to 6 R
30551
40545 ~
40551
30556
Module reset status, 1: power-on, 2: watchdog, 3:
40556
software reset command
Only for Modbus TCP protocol
40558
Ethernet host watchdog timeout value, 5 to 65535,
in second, 0 to disable.
Only for Modbus TCP protocol
30559
Ethernet host watchdog timeout count.
40559
Only for Modbus TCP protocol
30560
Module name, 0x0110
40560
Only for Modbus TCP protocol
DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual
Attribute
R/W
R/W
R/W
R/W
R
R/W
R
R
Version 1.1.3 Dec 2020 - 70 -