"Functional range" shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a
particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
Number
Size
I/O
1
1 Bit
C - - T -
2
1 Bit
C - - T -
3
1 Bit
C - - T -
4
1 Byte
C - - T -
5
1 Byte
C - - T -
6
1 Byte
C - - T -
7
1 Bit
C - - T -
https://www.zennio.com
Flags
Data type (DPT)
Functional Range
DPT_Alarm
DPT_Alarm
DPT_Switch
DPT_Scaling
DPT_SceneNumber
DPT_HVACMode
DPT_Trigger
Name
0/1
Alarm: Tamper
0/1
Alarm: Battery (Status)
0/1
Motion (Binary)
0% - 100%
Motion (Scaling)
0 - 63
Motion (Scene)
0=Auto
1=Comfort
2=Standby
Motion (HVAC)
3=Economy
4=Building
Protection
0/1
[Heartbeat] Object to Send '1'
Function
0 = No Alarm; 1 = Alarm
0 = No Alarm; 1 = Alarm
Binary Value
0 - 100%
Scene Value
Auto, Comfort, Standby, Economy, Building Protection