Annex I. Communication Objects - Zennio Presentia C v2 Manual

Presence detector with luminosity sensor for ceiling mounting
Hide thumbs Also See for Presentia C v2:
Table of Contents

Advertisement

ANNEX I. COMMUNICATION OBJECTS

"Functional range" shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have
a particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
Number
Size
1
1 Bit
2
1 Byte
3
1 Byte
4
2 Bytes
5
2 Bytes
6
2 Bytes
1 Bit
10
1 Bit
1 Bit
11
1 Bit
1 Bit
12
1 Bit
13
1 Byte
14
1 Byte
15
1 Bit
16
1 Bit
17
2 Bytes
18
2 Bytes
1 Bit
19
1 Bit
20
1 Bit
21
1 Byte
22
1 Byte
23
1 Byte
24
1 Byte
https://www.zennio.com/
I/O
Flags
Data type (DPT)
C - - T -
DPT_Trigger
I
C - W - -
DPT_SceneNumber
C - - T -
DPT_SceneControl
I/O
C R W - -
1.xxx
I/O
C R W - -
1.xxx
O
C R - T -
DPT_Value_Lux
I
C - W - -
DPT_DayNight
I
C - W - -
DPT_DayNight
I
C - W - -
DPT_Enable
I
C - W - -
DPT_Enable
O
C R - T -
DPT_Switch
C - - T -
DPT_Start
O
C R - T -
DPT_Scaling
O
C R - T -
DPT_HVACMode
I
C - W - -
DPT_Window_Door
I
C - W - -
DPT_Start
I
C - W - -
DPT_TimePeriodSec
I
C - W - -
DPT_TimePeriodSec
I
C - W - -
DPT_Enable
I
C - W - -
DPT_Enable
O
C R - T -
DPT_Occupancy
I
C - W - -
DPT_Scaling
I
C - W - -
DPT_Scaling
I
C - W - -
DPT_Scaling
I
C - W - -
DPT_Scaling
Functional Range
0/1
[Heartbeat] Object to Send '1'
0 - 63
Scene Input
0-63; 128-191
Scene Output
0/1
Correction Factor - Internal Sensor
0/1
Offset - Internal Sensor
Luminosity - Internal Sensor
0/1
Day/Night
0/1
Day/Night
0/1
Detection LEDs
0/1
Detection LEDs
0/1
Occupancy: Output (Binary)
0/1
Occupancy: Slave Output
0% - 100%
Occupancy: Output (Scaling)
1=Comfort
2=Standby
3=Economy
Occupancy: Output (HVAC)
4=Building
Protection
0/1
Occupancy: Trigger
0/1
Occupancy: Slave Input
0 - 65535
Occupancy: Waiting Time
0 - 65535
Occupancy: Listening Time
0/1
Occupancy: Lock
0/1
Occupancy: Lock
0/1
Occupancy: Occupancy State
0% - 100%
Sensor 1 Sensitivity
0% - 100%
Sensor 2 Sensitivity
0% - 100%
Sensor 3 Sensitivity
0% - 100%
Sensor 4 Sensitivity
Name
Function
Sending of '1' Periodically
Scene Value
Scene Value
[0, 80] x0.1
[-200, 200] Luxes
Luxes
0 = Day; 1 = Night
0 = Night; 1 = Day
0 = Disable; 1 = Enable
0 = Disable; 1 = Enable Only During
the Day
Binary Value
1 = Motion Detected
0-100%
Auto, Comfort, Standby, Economy,
Building Protection
Binary Value to Trigger the Occupancy
Detection
1 = Detection from slave device
0-65535 s.
1-65535 s.
0 = Unlock; 1 = Lock
0 = Lock; 1 = Unlock
0 = Not Occupied; 1 = Occupied
1-100%
1-100%
1-100%
1-100%
Technical Support:
https://support.zennio.com/
Presentia C v2
11