Annex I. Communication Objects - Zennio Presentia C v2 User Manual

Presence detector with luminosity sensor for ceiling mounting
Hide thumbs Also See for Presentia C v2:
Table of Contents

Advertisement

ANNEX I. COMMUNICATION OBJECTS

"Functional range" shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have
a particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
Number
1
2
3
4
5
6
10
11
12
13
14
15
16
17
18
19
20
21, 22, 23, 24
25, 35, 45, 55, 65, 75
26, 36, 46, 56, 66, 76
http://www.zennio.com
Size
I/O
Flags
Data type (DPT)
1 Bit
C T - - -
DPT_Trigger
1 Byte
I
C - - W -
DPT_SceneNumber
1 Byte
C T - - -
DPT_SceneControl
2 Bytes I/O
C - R W -
DPT_Coefficient
2 Bytes I/O
C - R W -
DPT_Luminosity_Offset
2 Bytes
O
C T R - -
DPT_Value_Lux
1 Bit
I
C - - W -
DPT_DayNight
1 Bit
I
C - - W -
DPT_DayNight
1 Bit
I
C - - W -
DPT_Enable
1 Bit
I
C - - W -
DPT_Enable
1 Byte
O
C T R - -
DPT_Scaling
1 Byte
O
C T R - -
DPT_HVACMode
1 Bit
O
C T R - -
DPT_Switch
1 Bit
C T - - -
DPT_Trigger
1 Bit
I
C - - W -
DPT_Window_Door
1 Bit
I
C - - W -
DPT_Trigger
2 Bytes
I
C - - W -
DPT_TimePeriodSec
2 Bytes
I
C - - W -
DPT_TimePeriodSec
1 Bit
I
C - - W -
DPT_Enable
1 Bit
I
C - - W -
DPT_Enable
1 Bit
O
C T R - -
DPT_Occupancy
1 Byte
I
C - - W -
DPT_Scaling
1 Bit
I
C - - W -
DPT_Trigger
1 Byte
O
C T R - -
DPT_Scaling
Functional Range
0/1
[Heartbeat] Object to Send '1'
0 - 63
Scene Input
0-63; 128-191
Scene Output
Correction Factor - Internal
Sensor
Offset - Internal Sensor
-671088.64 - 670760.96
Luminosity - Internal Sensor
0/1
Day/Night
0/1
Day/Night
0/1
Detection LEDs
0/1
Detection LEDs
0% - 100%
Occupancy: Output (Scaling)
1=Comfort
2=Standby
Occupancy: Output (HVAC)
3=Economy
4=Building Protection
0/1
Occupancy: Output (Binary)
0/1
Occupancy: Slave Output
0/1
Occupancy: Trigger
0/1
Occupancy: Slave Input
0 - 65535
Occupancy: Waiting Time
1 - 65535
Occupancy: Listening Time
0/1
Occupancy: Lock
0/1
Occupancy: Lock
0/1
Occupancy: Occupancy State
0% - 100%
Sensor x Sensitivity
0/1
[Cx] External Motion Detection
0% - 100%
[Cx] Output (Scaling)
Name
Function
Sending of '1' Periodically
Scene Value
Scene Value
[0, 80] x0.1
[-200, 200] Luxes
Luxes
0 = Day; 1 = Night
0 = Night; 1 = Day
0 = Disable; 1 = Enable
0 = Disable; 1 = Enable Only During
the Day
0-100%
Auto, Comfort, Standby, Economy,
Building Protection
Binary Value
1 = Motion Detected
Binary Value to Trigger the Occupancy
Detection
0 = 1 = Detection from slave device
0-65535 s.
1-65535 s.
0 = Unlock; 1 = Lock
0 = Lock; 1 = Unlock
0 = Not Occupied; 1 = Occupied
1-100%
0 = 1 = Motion detected by an
external sensor
0-100%
Technical Support:
http://support.zennio.com
Presentia C v2
10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zpdc30lv2

Table of Contents