Outdoor Unit Wiring - EAS Electric EFMV2 Series Instruction Manual

Floor-ceiling air conditioning unit
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 35
(B)
Indoor unit
power wires
Outdoor unit
Indoor & Outdoor
connective
wires
(purchased
separately)
(C)
Air switch
(purchased separately)
Indoor unit power wires
Outdoor unit power wires
Outdoor
unit
Indoor & Outdoor
connective
wires
(purchased
separately)
(D)
(Only for the North American)
Air switch
(purchased seperately)
Outdoor unit power wires
Outdoor unit
Air switch
(purchased separately)
NOTE: The cographs are for expla-
nation purpose only.
chine may be slightly different.
The actual shape shall prevail.
Air switch
(purchased
separately)
Indoor
unit
Air switch
(purchased
separately)
Indoor
unit
Indoor & Outdoor
connective wires
(purchased separately)
Indoor
unit
Your ma-
31

Outdoor Unit Wiring

WARNING
Before performing any electrical or
wiring work, turn off the main
power to the system.
1. Prepare the cable for connection
a. You must first choose the right
cable size. Be sure to use H07RN-
F cables.
NOTE: In North America, choose the
cable type according to the local
electrical codes and regulations.
Minimum Cross-Sectional Area of Power
and Signal Cables (For reference)
Rated Current of
Appliance (A)
> 3 and ≤ 6
> 6 and ≤ 10
> 10 and ≤ 16
> 16 and ≤ 25
> 25 and ≤ 32
> 32 and ≤ 40
CHOOSE THE RIGHT CABLE SIZE
The size of the power supply
cable, signal cable, fuse, and switch
needed is determined
maximum current of the unit. The
maximum current is indicated on
the nameplate located on the side
panel of the unit. Refer to this
nameplate to choose the right
cable, fuse, or switch.
NOTE: In North America, please
choose the right cable size accor-
ding to the Minimum Circuit Am-
pacity indicated on the nameplate
of the unit.
b.
Using wire strippers, strip the
rubber jacket from both ends of the
signal cable to reveal approxima-
tely 15cm (5.9") of wire.
c. Strip the insulation from the ends.
d.
Using a wire crimper, crimp u-
lugs on the ends.
Nominal Cross-Sectional
Area (mm²)
0.75
1
1.5
2.5
4
6
by
the
V.1