4. OUTDOOR UNIT INSTALLATION

WARNING
Ask an authorized dealer or qualified installation professional to
install maintain the air conditioner.Inappropriate installation may
result in water leakage,electric shock or fire.
Do not expose the unit directly to sunlight and other souces of heat.
Add a cover if necessary to prevent the unit from direct sunlight.
A place that is even and strong enough to bear the weight of the
unit.
Do not install in a place that might increase the vibration of the unit.
Install the unit at a place where noise and hot air couldn't bother
your neighbour.
Do not install the air conditioner in a location subject to a risk of
exposure to a combustible gas. If a combustible gas leaks, and
stays around the unit, a fire may occur.
Remove obstacles around the unit in order to leave enough space
for air circulation.
Install the unit near to the indoor unit as faras possible under
certain installation conditions.
When installing the outdoor unit in a place that is constantly
exposed to a strong wind such as the upper stairs or rooftop of
a building, use a baffle when necessary.
Install the unit so that its discharge port faces to the wall of the
building. Keep a distance of 4000mm or more between the unit and
the wall surface. Keep strong wind from blowing back inside.
Do not mount the outdooor unit on a wall.
4.1 Installation place
Please keep away from the following place, or malfunction of the
machine may be caused:
There is combustible gas leakage.
There is much oil (including engine oil) ingredient.
There is salty air surrounding(near the coast)
There is caustic gas (the sulfide, for example) existing in the
air (near a hotspring)
A place the heat air expelled out from the outdoor unit can
reach your neighbor's window.
A place that the noise interferes your neighbors every day life.
A place that is too weak to bear the weight of the unit
Uneven place.
Insufficient ventilation place.
Near a private power station or high Frequency equipment.
Install indoor unit, outdoor unit, power cord and connecting
wire at least 1m away from TV set or radio to prevent noise or
picture interference.
Installation space (Unit:mm), see Fig.4-1,4-2,4-3,4-4.
(Wall or obstacle)
Air inlet
>400
Air inlet
strong wind
>600
Air outlet
>4000
>400
>4000
4.2 Handling
1)Do not unpacking the unit when handling. Use two ropes whose
lengths are more than 8m to handle the unit. Keep balance of the
unit, when lifting stably. Use a padding plate or packing materials
for protection if the package has been destroyed or no package.
2)Keep the unit vertical when moving and handling. If the unit
barycenter is not at the center of the unit, do not lean it more than
30°. Refer to Fig.4-5. Be careful during moving and lifting .
3)Never hold the inlet of the outdoor unit to prevent it from deforming.
4)Do not touch the fan with hands or other objects.
5)Do not lean it more than 45°, and do not lay it sidelong.
Rope
Maintain
channel
Fig.4-1
5
>1000
>8000
>6000
>600
Do not unpacking
Position of barycenter
Make the rope go through the
lifting holes from both right and
left sides in the wooden collet
Fig.4-2
>400
Fig.4-3
Fig.4-4
Fig.4-5