Multi-Groups System Parameter (Max. 6 Groups Per System) - Pylontech Force-H1-V2 Operation Manual

Lithium-ion phosphate energy storage system
Table of Contents

Advertisement

2.2.1.2 Multi-groups system parameter (Max. 6 groups per system)

For multi-groups operation, please make sure the battery type in the whole system is the same,
please make sure the battery amount of each group is the same.
Product Type
Battery System Voltage(Vdc)*
Battery System group amount(pcs)
Battery System capacity (AH)
Battery System Operation
Current(Amps, Standard)
Battery System Operation
Current(Amps, Normal)
Battery System Operation Current
(Amps, Max.@15s)
P-Combiner-HV-3/6 Operation
Current (Amps, Normal)
P-Combiner-HV-3/6 Operation
Current (Amps, Max.@15s)
*The Battery System Voltage is varying depends on battery amount in serial per group.
**The current is based on BMS theoretical operation current to consider. If use P-Combiner-HV-
3 as the combiner box of the multi-groups` battery system wiring connection, the max.
continuous operation current is 50Amps, max. peak operation current is 80Amps for 15sec. for
the battery system. Please make sure the real operation current not exceed the combiner box
power rating.
***The current is based on BMS theoretical operation current to consider. If use P-Combiner-
HV-6 as the combiner box of the multi-groups` battery system wiring connection, the max.
continuous operation current is 100Amps, max. peak operation current is 160Amps for 15sec.
for the battery system. Please make sure the real operation current not exceed the combiner
box power rating.
Force-H1-V2 in multi-groups
96/144 / 192 / 240 / 288 / 336
2
3
148
222
29.6
44.4
74**
111**
148***
84**
126**
168***
50
80
9
4
5
296
370
59.2
74
185***
222***
210***
252***
100
160
6
444
88.8

Advertisement

Table of Contents
loading

Table of Contents