Troubleshooting
March 2023
Recommended actions
6.4.4 
Diagnostic message: Maintenance Required
Process Alert 1
The device has detected a change in the monitored variable that exceeds the configured
thresholds for Process Alert 1.
Graphical LCD
display
LCD display
Local operator
interface (LOI)
Recommended actions
Process Alert 2
The device has detected a change in the monitored variable that exceeds the configured
thresholds for Process Alert 2.
Graphical LCD
display
LCD display
Local operator
interface (LOI)
Recommended actions
Plugged Impulse Line Diagnostic
The plugged impulse line diagnostic has detected a change in process noise levels, which
could be attributed to a plugged impulse line, plugged flow element, or agitation loss.
Graphical LCD
display
LCD display
Local operator
interface (LOI)
90
1. Verify the conditions of the process where the transmitter is installed.
2. Verify the settings for the 4 mA and 20 mA range points and readjust if
necessary.
3. Check the transmitter pressure connection to ensure it is not plugged and the
isolating diaphragms are not damaged.
4. Replace the sensor module.
Process Alert 1 [Alert Name]
[Alert Name]
[Alert Name]
1. Verify that the monitored variable is beyond the alert values.
2. Modify the alert settings or turn off the alert.
Process Alert 2 [Alert Name]
[Alert Name]
[Alert Name]
1. Verify that the monitored variable is beyond the alert values.
2. Modify the alert settings or turn off the alert.
Plugged Impulse Line Diagnostic
Plug Line
Plugged Line